Customization: | Available |
---|---|
Type: | High-voltage |
Installation: | Indoor High-voltage |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make at Made-in-china.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical Parameters 12KV | ||
Content | Unit | Parameter |
Rated Voltage | KV | 12 |
Rated frequency | HZ | 50 |
Rated currency | A | 630 |
Rated short circuit withstand current | KA | 20/25 |
Rated peak withstand current | KA | 63 |
Rated short circuit duration | s | 2 |
Rated short circuit cloing current | KA | 63 |
Mechnicial life | Time | 10000 |
Open triphase dissimilar | ms | ≤2 |
Closing triphase dissimilar | ms | ≤2 |
Opening average speed | mis | 3-6 |
Closing average speed | m/s | 4-6 |
Air working step pressure fracture: 22KV -28KV/1min | ||
The primary loop resistance: A phase B phase C phase(load switch circuit resistance ≤40μΩ) | ||
Grounding resistance: A phase B phase C phase (grounding resistance load switch ≤500μΩ) |