Customization: | Available |
---|---|
Application: | Industrial, Power Station |
Voltage: | 12/15kv |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Application:
For connection of polymeric cable to transformers, switch gear, motors and other equipment with a pre-moulded separable connector.
For indoor and outdoor installations.
System voltage up to 24 kV.
Continuous current 630 A (900 A overload for 8 hours).
Cable particulars:
- Polymeric cable (XLPE, EPR, etc.)
- Copper or aluminum conductors
- Semiconducting or metallic screens
- Conductor size 12kV 25-120 mm2 24kV 25-400 mm²
Features:
Provides a fully screened and fully submersible separable connection when mated with the proper bushing or plug.
Can be used under the circumstances
Built-in capacitance test point to determine the circuit status or install a fault indicator.
No minimum phase clearance requirements.
Mounting can be vertical, horizontal, or any angle in between.
Installation:
Without any special tools
When finish the installation of elbow connector, the power can be supply directly.
According to the Installation Instruction Sheet
(any other special requirement, please contact our sales engineer)
Reference No. |
Conductor Cross Section(mm²) |
stretch range over insulation(mm) |
AH QJ-12/630-25 |
25 |
16.6 |
AH QJ-12/630-35 |
35 |
17.6 |
AH QJ-12/630-50 |
50 |
19 |
AH QJ-12/630-70 |
70 |
20.6 |
AH QJ-12/630-95 |
95 |
22.2 |
AH QJ-12/630-120 |
120 |
23.6 |
AH QJ-12/630-150 |
150 |
25.2 |
AH QJ-12/630-185 |
185 |
26.7 |
AH QJ-12/630-240 |
240 |
29 |
AH QJ-12/630-300 |
300 |
31.2 |
AH QJ-12/630-400 |
400 |
34.4 |
AH QJ-12/630-500 |
500 |
37.2 |
Reference No. |
Conductor Cross Section(mm²) |
stretch range over insulation(mm) |
AH QJ-24/630-35 |
35 |
18.6 |
AH QJ-24/630-50 |
50 |
19.6 |
AH QJ-24/630-70 |
70 |
21 |
AH QJ-24/630-95 |
95 |
22.6 |
AH QJ-24/630-120 |
120 |
24.2 |
AH QJ-24/630-150 |
150 |
25.6 |
AH QJ-24/630-185 |
185 |
27.2 |
AH QJ-24/630-240 |
240 |
28.7 |
AH QJ-24/630-300 |
300 |
31.1 |
AH QJ-24/630-400 |
400 |
33.2 |